ABB 7524A63G05

ABB Type CLE Current Transformer Model 7524A63G05 User Manual

Pitunjuk pikeun Pamasangan, Operasi, sareng Pangropéa

1. Bubuka

This user manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB Type CLE Current Transformer, Model 7524A63G05. This device is designed for accurate current measurement in industrial electrical systems. Please read this manual thoroughly before attempting any procedures to ensure proper handling and to prevent potential hazards.

2. Produk Langkungview

The ABB Type CLE Current Transformer (CT) is a critical component for monitoring and protecting electrical circuits. It safely steps down high primary currents to a measurable level for instruments, meters, and relays. The Model 7524A63G05 features a robust design suitable for demanding industrial environments.

ABB Type CLE Current Transformer, front-side view

Gambar 2.1: Sacara umum view of the ABB Type CLE Current Transformer. This image displays the robust, dark-colored casing and the transparent terminal cover on top, indicating the primary and secondary connections. The toroidal shape allows for easy integration around a primary conductor.

ABB Type CLE Current Transformer, angled view

Gambar 2.2: Lain angled view of the ABB Type CLE Current Transformer, highlighting its compact design and the mounting points on the base. The nameplate is visible on the side, providing key operational specifications.

Close-up of ABB Type CLE Current Transformer terminal block and nameplate

Gambar 2.3: A detailed close-up of the terminal block and the product nameplate. The transparent cover protects the secondary terminals (X1, X2) and shows the connection points. The nameplate clearly displays the model number, current ratio, and other electrical specifications.

Diwincik view of ABB Type CLE Current Transformer nameplate

Gambar 2.4: An extreme close-up of the ABB Type CLE Current Transformer's nameplate. This view allows for clear reading of critical data such as "TYPE CLE", "CURRENT TX.", "S# 7524A63G05", "RATIO 6000:5 AMPS", "60 HZ", "NSV 0.6 KV", "BIL 10 KV", and "ANSI ACC. CL. METERING 0.3 B0.1 THRU B1.8". It also indicates "Made in U.S.A." and the manufacturer "ABB Power T&D Company Inc."

3. Émbaran Kasalametan

PERHATOSAN: Bahaya sengatan listrik. Pamasangan sareng pangropéa ngan ukur kedah dilakukeun ku tanaga anu mumpuni.

  • Always de-energize the primary circuit before installing or servicing the current transformer.
  • Never open the secondary circuit of an energized current transformer. This can lead to dangerously high voltages and potential injury or equipment damage.
  • Pastikeun sadaya sambungan aman sareng insulated leres.
  • Verify the correct polarity before connecting the CT to metering or protection devices.
  • Anggo alat pelindung diri (APD) anu pantes nalika damel sareng sistem listrik.

4. Setup jeung Instalasi

Installation of the ABB Type CLE Current Transformer requires adherence to local electrical codes and safety standards. It is recommended that a certified electrician or qualified technician perform the installation.

  1. Sirkuit De-énergize: Ensure the primary circuit where the CT will be installed is completely de-energized and locked out according to safety protocols.
  2. Pamasangan: Securely mount the CT using appropriate hardware. The CT is designed to encircle the primary conductor.
  3. Primary Conductor: Pass the primary conductor through the center opening of the current transformer.
  4. Secondary Connections: Connect the secondary terminals (X1 and X2) to the metering or protection device. Observe correct polarity as indicated on the nameplate (H1-H2 for primary, X1-X2 for secondary). X1 typically corresponds to H1, and X2 to H2.
  5. Grounding: Ensure the secondary circuit of the CT is properly grounded at one point, typically at the X2 terminal, to prevent high voltage ngawangun.
  6. Pariksa sambungan: Double-check all wiring for correctness and tightness.
  7. Re-energize: Once installation is complete and verified, the primary circuit can be safely re-energized.

5. Parentah Operasi

The ABB Type CLE Current Transformer operates passively by inducing a proportional current in its secondary winding based on the primary current flowing through its core. Once installed, it requires no active user intervention for its primary function.

  • Ngawaskeun: The output of the CT (typically 5 Amps at rated primary current) is fed into a connected meter, relay, or other monitoring device. Refer to the instruction manual of the connected device for its operation.
  • Load (Burden): Ensure the connected load (burden) on the secondary circuit does not exceed the CT's rated burden (e.g., B0.1 through B1.8 as indicated on the nameplate). Exceeding the burden can lead to inaccurate readings and potential damage.
  • Polaritasna: Correct polarity is crucial for accurate directional measurements and proper operation of protective relays.

6. Pangropéa

The ABB Type CLE Current Transformer is designed for long-term, reliable operation with minimal maintenance. However, periodic inspections are recommended to ensure optimal performance and safety.

  • Inspeksi Visual: Periodically inspect the CT for any signs of physical damage, discoloration, or loose connections.
  • beberesih: If necessary, gently clean the exterior of the CT with a dry, lint-free cloth. Do not use abrasive cleaners or solvents. Ensure the power is off before cleaning.
  • Pariksa Terminal: Verify that all secondary terminal connections remain tight and free from corrosion. This should only be done with the primary circuit de-energized and the secondary circuit shorted or connected to a safe load.
  • Kaayaan Lingkungan: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature degradation.

7. Cara ngungkulan

Most issues related to current transformers stem from improper installation or external circuit problems. Always prioritize safety when troubleshooting.

MasalahMungkin Cukang lantarananaSolusi
No output from CT / Incorrect readings
  • Open secondary circuit
  • Incorrect wiring/polarity
  • Primary circuit de-energized
  • Faulty connected meter/device
  • CT burden exceeded
  • De-energize primary circuit. Check secondary connections for continuity and ensure they are properly terminated.
  • Verify wiring against schematic and nameplate.
  • Confirm primary circuit is energized and current is flowing.
  • Test connected device independently.
  • Reduce secondary load or replace CT with appropriate burden rating.
Overheating of CT
  • Overcurrent in primary circuit
  • Excessive secondary burden
  • Short circuit in secondary winding
  • Check primary circuit load.
  • Reduce secondary load.
  • De-energize primary circuit. Inspect secondary wiring for shorts.

If troubleshooting steps do not resolve the issue, contact ABB technical support or a qualified service professional.

8. Spésifikasi

The following specifications apply to the ABB Type CLE Current Transformer, Model 7524A63G05:

  • Jumlah modél: 7524A63G05
  • merek: ABB (Asea Brown Boveri / ABB Power T&D Company Inc.)
  • Tipe: CLE Current Transformer
  • Current Ratio: 6000:5 Amps
  • Frékuénsi: 60 Hz
  • Sistim nominal Voltage (NSV): 0.6 kV
  • Basic Impulse Level (BIL): 10 kV
  • ANSI Accuracy Class: Metering 0.3 B0.1 THRU B1.8
  • Ukuran Luar: Kira-kira 12" x 13" x 3" (30.5 cm x 33 cm x 7.6 cm)
  • Inside Dimensions (Window): Kira-kira 8" x 8" x 3" (20.3 cm x 20.3 cm x 7.6 cm)
  • Nomer Bagian Pabrikan: 236P750H07
  • UPC: 782451081325

9. Garansi jeung Rojongan

For information regarding warranty coverage, technical support, or service for your ABB Type CLE Current Transformer, Model 7524A63G05, please contact ABB directly through their official website or customer service channels. Ensure you have your model number and any purchase details available when contacting support.

You can visit the official ABB websitus pikeun inpormasi lengkep: www.abb.com

Dokumén Patali - 7524A63G05

Praview ABB Ayeuna jeung Voltage Instrumen Transformers: Pamasangan, Pamakéan, sareng Pitunjuk Pangropéa
Comprehensive guide from ABB detailing the installation, technical specifications, safety instructions, and maintenance procedures for Current and Voltage (potential) Instrument Transformers. It covers indoor and outdoor applications.
Praview ABB RET650 Transformer Protection Relay - Guide produk
Jelajahi ABB RET650, relay panyalindungan trafo serbaguna anu nawiskeun diferensial maju, impedansi, arus, voltage, jeung panyalindungan frékuénsi pikeun sistem kakuatan. Pituduh produk ieu ngawincik fitur-fiturna, aplikasi, sareng spésifikasi téknis pikeun otomatisasi gardu induk anu dipercaya.
Praview ABB FH200A System pro M compact Residual Current Circuit Breaker: Installation and Technical Data
Comprehensive guide to the ABB FH200A System pro M compact residual current circuit breaker, covering technical specifications, installation procedures, electrical connections, and safety instructions.
Praview ABB DSH201R RCBO: Technical Data Sheet & Specifications
Comprehensive technical datasheet for the ABB DSH201R Residual Current Breaker with Overcurrent protection (RCBO). Details include 4.5kA breaking capacity, AC type, 30mA sensitivity, C tripping characteristics, and rated current options from 6 to 40A. Features application benefits, detailed electrical and mechanical specifications, performance data under various conditions, dimensions, and connection diagrams.
Praview ABB PSE Softstarters: Features, Specifications, and Benefits for Industrial Motor Control
Explore the ABB PSE Softstarters, a series of compact digital soft starters offering advanced motor control, protection, and automation integration. This document details their technical specifications, key features like integrated motor protection and torque control, and real-world application benefits for various industries.
Praview ABB B21/B23/B24 Installation Manual
This installation manual from ABB provides detailed instructions for the B21, B23, and B24 series energy meters. It covers essential aspects such as mounting procedures, electrical connections for different models, basic settings configuration, and comprehensive technical specifications.