This manual provides detailed instructions for the proper use, setup, operation, maintenance, and troubleshooting of the Elitech VG-760 Digital HVAC Micron Vacuum Gauge. This device is designed for accurate vacuum measurement in HVAC and refrigeration systems, ensuring efficient and reliable performance.

The Elitech VG-760 is a robust digital vacuum gauge featuring a wide measurement range, high accuracy, and multiple measurement units. It is built with an IP65 rating for enhanced protection against environmental factors.

2. Émbaran Kasalametan

  • Always wear appropriate personal protective equipment (PPE) when working with HVAC/R systems.
  • Ensure the system is depressurized before connecting or disconnecting the vacuum gauge.
  • Do not expose the gauge to extreme temperatures or corrosive substances.
  • Handle the gauge with care to prevent damage to the sensor.
  • Jauhkeun alat ti barudak.

3. Produk Langkungview

The Elitech VG-760 Digital HVAC Micron Vacuum Gauge is designed for precise vacuum measurement. Its compact design and clear display make it suitable for various applications.

Elitech VG-760 Digital Vacuum Gauge

Figure 1: Elitech VG-760 Digital Vacuum Gauge, showing its compact design and digital display.

3.1 Fitur konci

  • Wide Measurement Range: 0-19000 Microns.
  • High Accuracy: ±10% or ±10 Micron.
  • Multiple Measurement Units: inHg, Torr, psi, mbar, mTorr, Pa, micron, Kpa.
  • Settable High/Low Pressure Alarms.
  • IP65 Rated for enhanced protection.
  • Long Battery Life: Up to 300 hours with 3 AA batteries.

3.2 Display and Button Functions

Elitech VG-760 display and button functions

Figure 2: Elitech VG-760 display elements and button controls. 1. Battery Level, 2. Auto OFF (15 min), 3. Current Vacuum Value, 4. Units. Buttons: A (Backlight on/off), B (Power on/off), C (Switch units). Pressing A+B enables auto-off.

Elitech VG-760 display showing 8 units

Figure 3: The Elitech VG-760 supports 8 different measurement units: inHg, Torr, psia, mbar, mTorr, Pa, micron, and kPa.

3.3 Filtering Components

Elitech VG-760 multiple filtering components

Angka 4: Ngabeledug view of the Elitech VG-760's multiple filtering system, including the O-ring, Filter Net, Filter Cotton, and 1/4" SAE Fitting, designed to protect the sensor from contaminants.

4. Setélan

4.1 Ngabongkar bungkusan

Upon receiving your Elitech VG-760, carefully unpack all components. The packing list typically includes:

Elitech VG-760 packing list and contents

Figure 5: Contents of the Elitech VG-760 package, including the vacuum gauge, user manual, AA batteries, zip bag, filter cotton, filter net, and O-rings.

  • 1 x Vacuum Gauge
  • 1 x Manual Pamaké
  • 3 x Batré AA
  • 1 x Zip Bag
  • 2 x Filter Cotton & Filter Net
  • 2 x O-cingcin

4.2 Pamasangan batré

  1. Locate the battery compartment on the back of the gauge.
  2. Buka panutup kompartemen.
  3. Selapkeun 3 batré AA, mastikeun polaritasna bener.
  4. Tutup panutup kompartemen batré aman.

4.3 Connecting to the System

The VG-760 features a 1/4" SAE male flare fitting for connection to HVAC/R systems. Ensure all connections are tight to prevent leaks.

Video 1: Demonstrates how to connect the Elitech VG-760 to an HVAC system using a T-connector and bend adapter for vacuum measurement. It highlights the oil-proof film protection on the sensor and the process of attaching the gauge to a vacuum pump.

  1. Attach the VG-760 to the system using appropriate fittings (e.g., T-connector and bend adapter).
  2. Ensure the connection is secure and leak-free.

5. Parentah Operasi

5.1 Daya Hurung/Pareuman

Pencét éta Kakuatan button (center button) to turn the gauge on or off.

5.2 Kadali lampu tukang

Pencét éta Lampu tukang button (left button) to toggle the display backlight on or off for improved visibility in various lighting conditions.

5.3 Switching Measurement Units

Pencét éta UNIT button (right button) to cycle through the available measurement units: inHg, Torr, psi, mbar, mTorr, Pa, micron, and Kpa.

5.4 Fungsi Otomatis-Pareum

The gauge features an auto-off function to conserve battery life. To enable or disable this feature, press and hold both the Lampu tukang jeung Kakuatan tombol sakaligus.

5.5 Nafsirkeun Bacaan

The gauge displays the vacuum value in real-time. If the display shows dashes (-----), it indicates that the current pressure exceeds the measurement range of the gauge (above 19,000 microns).

6. Pangropéa

6.1 Sensor beberesih

If the vacuum gauge sensor becomes contaminated with oil, it may display no value or inaccurate readings. In such cases, it is necessary to clean the vacuum sensor.

Video 2: Illustrates the importance of cleaning the vacuum sensor if it becomes contaminated with oil, as contamination can prevent accurate readings. The video shows how to access and clean the sensor using a solvent.

  1. Disconnect the gauge from the system.
  2. Carefully remove the 1/4" SAE fitting to expose the sensor.
  3. Use a suitable solvent (e.g., isopropyl alcohol) and a lint-free cloth or cotton swab to gently clean the sensor surface.
  4. Allow the sensor to dry completely before reassembling.
  5. Replace the O-ring, filter net, and filter cotton as needed to ensure proper sealing and filtration.

6.2 Perawatan Umum

  • Store the gauge in its protective zip bag when not in use.
  • Avoid dropping or subjecting the gauge to strong impacts.
  • Ngusap luar ku hipu, damp lawon sakumaha diperyogikeun. Entong nganggo pembersih anu abrasif.

7. Cara ngungkulan

MasalahMungkin Cukang lantarananaSolusi
Gauge teu hurungBatré paéh atawa salah dipasangGanti batré atanapi pariksa polaritasna
Display shows dashes (-----)Pressure is above 19,000 microns (out of range)Continue evacuation until pressure drops within range
Inaccurate or no readingContaminated sensor (oil, debris)Clean the vacuum sensor as per maintenance instructions
Inaccurate or no readingSystem leakCheck all connections for leaks and repair as necessary

8. Spésifikasi

Elitech VG-760 dimensions and technical specifications

Figure 6: Elitech VG-760 dimensions and key technical specifications.

ParameterNilai
Dimensi produk4.92 x 1.38 x 2.76 inci
Item Beurat15.52 Ounces (0.6 lbs)
Nomer Modél ItemVG-760
Batré3 batré AA (kaasup)
ProdusénElitech
Bahanpalastik
Rentang Ukur0-19000 mikron
Akurasi±10% or ±10 Micron
Suhu Operasi0 ° F ~ 140 ° F (-17.8 ° C ~ 60 ° C)
Pas1/4" SAE Male Flare
Kahirupan batréNepi ka 300 jam
Tingkat panyalindunganIP65 Dipeunteun

9. Émbaran jaminan

Elitech products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the warranty card included with your product or contact Elitech customer support. Keep your purchase receipt as proof of purchase for warranty claims.

10. Rojongan Palanggan

For technical assistance, troubleshooting, or any inquiries regarding your Elitech VG-760 Digital HVAC Micron Vacuum Gauge, please contact Elitech customer support.

  • Rojongan Email: Sadia 24/7
  • Rojongan Telepon: Available for US customers

Please visit the official Elitech websitus pikeun inpormasi kontak sareng sumber dukungan anu paling énggal.

Dokumén Patali - VG-760

Praview Elitech MS-100 Digital Manifold Gauge: Features, Operation, and Specifications
Comprehensive guide to the Elitech MS-100 Digital Manifold Gauge, covering its features, quick operation, technical specifications, precautions, and product details for HVAC and refrigeration systems.
Praview Elitech MS Series Digital Manifold Gauge User Manual
User manual for the Elitech MS Series digital manifold gauge, covering product description, general overview, button functions, specifications, quick start guide, operation steps, intelligent applications, and maintenance.
Praview Elitech MS-100 PLUS Smart Digital Manifold Gauge User Manual
Comprehensive user manual for the Elitech MS-100 PLUS Smart Digital Manifold Gauge, covering product introduction, safety instructions, overview, button functions, technical parameters, and quick operation guides for refrigeration and HVAC systems.
Praview VGW 760 Wireless Digital Vacuum Gauge User Manual
Comprehensive user manual for the Elitech VGW 760 Wireless Digital Vacuum Gauge, covering overview, features, specifications, operation instructions, cleaning, app usage, warnings, and package contents for HVAC and refrigeration applications.
Praview Elitech MS-100 Digital Manifold Gauge Manual Pamaké
Manual pamaké pikeun Elitech MS-100 Digital Manifold Gauge, detailing fitur, operasi, spésifikasi, sarta perawatan.
Praview Elitech MS-800 Series Digital Manifold Gauge User Manual & Specifications
Comprehensive user manual for the Elitech MS-800 Series digital manifold instrument, covering product introduction, safety guidelines, environmental protection, detailed specifications, and quick operation guides for pressure and temperature measurements, hold pressure tests, and refrigerant charging for HVAC and refrigeration systems.