This manual provides detailed instructions for the proper use, setup, operation, maintenance, and troubleshooting of the Elitech VG-760 Digital HVAC Micron Vacuum Gauge. This device is designed for accurate vacuum measurement in HVAC and refrigeration systems, ensuring efficient and reliable performance.
The Elitech VG-760 is a robust digital vacuum gauge featuring a wide measurement range, high accuracy, and multiple measurement units. It is built with an IP65 rating for enhanced protection against environmental factors.
2. Émbaran Kasalametan
- Always wear appropriate personal protective equipment (PPE) when working with HVAC/R systems.
- Ensure the system is depressurized before connecting or disconnecting the vacuum gauge.
- Do not expose the gauge to extreme temperatures or corrosive substances.
- Handle the gauge with care to prevent damage to the sensor.
- Jauhkeun alat ti barudak.
3. Produk Langkungview
The Elitech VG-760 Digital HVAC Micron Vacuum Gauge is designed for precise vacuum measurement. Its compact design and clear display make it suitable for various applications.

Figure 1: Elitech VG-760 Digital Vacuum Gauge, showing its compact design and digital display.
3.1 Fitur konci
- Wide Measurement Range: 0-19000 Microns.
- High Accuracy: ±10% or ±10 Micron.
- Multiple Measurement Units: inHg, Torr, psi, mbar, mTorr, Pa, micron, Kpa.
- Settable High/Low Pressure Alarms.
- IP65 Rated for enhanced protection.
- Long Battery Life: Up to 300 hours with 3 AA batteries.
3.2 Display and Button Functions

Figure 2: Elitech VG-760 display elements and button controls. 1. Battery Level, 2. Auto OFF (15 min), 3. Current Vacuum Value, 4. Units. Buttons: A (Backlight on/off), B (Power on/off), C (Switch units). Pressing A+B enables auto-off.

Figure 3: The Elitech VG-760 supports 8 different measurement units: inHg, Torr, psia, mbar, mTorr, Pa, micron, and kPa.
3.3 Filtering Components

Angka 4: Ngabeledug view of the Elitech VG-760's multiple filtering system, including the O-ring, Filter Net, Filter Cotton, and 1/4" SAE Fitting, designed to protect the sensor from contaminants.
4. Setélan
4.1 Ngabongkar bungkusan
Upon receiving your Elitech VG-760, carefully unpack all components. The packing list typically includes:

Figure 5: Contents of the Elitech VG-760 package, including the vacuum gauge, user manual, AA batteries, zip bag, filter cotton, filter net, and O-rings.
- 1 x Vacuum Gauge
- 1 x Manual Pamaké
- 3 x Batré AA
- 1 x Zip Bag
- 2 x Filter Cotton & Filter Net
- 2 x O-cingcin
4.2 Pamasangan batré
- Locate the battery compartment on the back of the gauge.
- Buka panutup kompartemen.
- Selapkeun 3 batré AA, mastikeun polaritasna bener.
- Tutup panutup kompartemen batré aman.
4.3 Connecting to the System
The VG-760 features a 1/4" SAE male flare fitting for connection to HVAC/R systems. Ensure all connections are tight to prevent leaks.
Video 1: Demonstrates how to connect the Elitech VG-760 to an HVAC system using a T-connector and bend adapter for vacuum measurement. It highlights the oil-proof film protection on the sensor and the process of attaching the gauge to a vacuum pump.
- Attach the VG-760 to the system using appropriate fittings (e.g., T-connector and bend adapter).
- Ensure the connection is secure and leak-free.
5. Parentah Operasi
5.1 Daya Hurung/Pareuman
Pencét éta Kakuatan button (center button) to turn the gauge on or off.
5.2 Kadali lampu tukang
Pencét éta Lampu tukang button (left button) to toggle the display backlight on or off for improved visibility in various lighting conditions.
5.3 Switching Measurement Units
Pencét éta UNIT button (right button) to cycle through the available measurement units: inHg, Torr, psi, mbar, mTorr, Pa, micron, and Kpa.
5.4 Fungsi Otomatis-Pareum
The gauge features an auto-off function to conserve battery life. To enable or disable this feature, press and hold both the Lampu tukang jeung Kakuatan tombol sakaligus.
5.5 Nafsirkeun Bacaan
The gauge displays the vacuum value in real-time. If the display shows dashes (-----), it indicates that the current pressure exceeds the measurement range of the gauge (above 19,000 microns).
6. Pangropéa
6.1 Sensor beberesih
If the vacuum gauge sensor becomes contaminated with oil, it may display no value or inaccurate readings. In such cases, it is necessary to clean the vacuum sensor.
Video 2: Illustrates the importance of cleaning the vacuum sensor if it becomes contaminated with oil, as contamination can prevent accurate readings. The video shows how to access and clean the sensor using a solvent.
- Disconnect the gauge from the system.
- Carefully remove the 1/4" SAE fitting to expose the sensor.
- Use a suitable solvent (e.g., isopropyl alcohol) and a lint-free cloth or cotton swab to gently clean the sensor surface.
- Allow the sensor to dry completely before reassembling.
- Replace the O-ring, filter net, and filter cotton as needed to ensure proper sealing and filtration.
6.2 Perawatan Umum
- Store the gauge in its protective zip bag when not in use.
- Avoid dropping or subjecting the gauge to strong impacts.
- Ngusap luar ku hipu, damp lawon sakumaha diperyogikeun. Entong nganggo pembersih anu abrasif.
7. Cara ngungkulan
| Masalah | Mungkin Cukang lantaranana | Solusi |
|---|---|---|
| Gauge teu hurung | Batré paéh atawa salah dipasang | Ganti batré atanapi pariksa polaritasna |
| Display shows dashes (-----) | Pressure is above 19,000 microns (out of range) | Continue evacuation until pressure drops within range |
| Inaccurate or no reading | Contaminated sensor (oil, debris) | Clean the vacuum sensor as per maintenance instructions |
| Inaccurate or no reading | System leak | Check all connections for leaks and repair as necessary |
8. Spésifikasi

Figure 6: Elitech VG-760 dimensions and key technical specifications.
| Parameter | Nilai |
|---|---|
| Dimensi produk | 4.92 x 1.38 x 2.76 inci |
| Item Beurat | 15.52 Ounces (0.6 lbs) |
| Nomer Modél Item | VG-760 |
| Batré | 3 batré AA (kaasup) |
| Produsén | Elitech |
| Bahan | palastik |
| Rentang Ukur | 0-19000 mikron |
| Akurasi | ±10% or ±10 Micron |
| Suhu Operasi | 0 ° F ~ 140 ° F (-17.8 ° C ~ 60 ° C) |
| Pas | 1/4" SAE Male Flare |
| Kahirupan batré | Nepi ka 300 jam |
| Tingkat panyalindungan | IP65 Dipeunteun |
9. Émbaran jaminan
Elitech products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the warranty card included with your product or contact Elitech customer support. Keep your purchase receipt as proof of purchase for warranty claims.
10. Rojongan Palanggan
For technical assistance, troubleshooting, or any inquiries regarding your Elitech VG-760 Digital HVAC Micron Vacuum Gauge, please contact Elitech customer support.
- Rojongan Email: Sadia 24/7
- Rojongan Telepon: Available for US customers
Please visit the official Elitech websitus pikeun inpormasi kontak sareng sumber dukungan anu paling énggal.