1. Bubuka
This manual provides detailed instructions for the installation, operation, and maintenance of the Elitech CP-6000N Current Monitoring Relay. The CP-6000N is designed for comprehensive electrical system protection, offering current monitoring, overload protection, phase monitoring, and temperature control capabilities with RS-485 communication.
2. Émbaran Kasalametan
Please read all safety instructions carefully before installation and operation. Failure to follow these instructions may result in equipment damage, personal injury, or death. Only qualified personnel should perform installation and maintenance.
- Disconnect all power sources before wiring or servicing the device.
- Pastikeun grounding ditangtoskeun pikeun nyegah shock listrik.
- Verify all connections are secure and correct according to the wiring diagram.
- Ulah ngoperasikeun alat ieu dina lingkungan anu ngaleuwihan kaayaan operasi anu ditangtukeun.
3. Produk Langkungview
The Elitech CP-6000N is an advanced current monitoring relay offering robust protection features for industrial and commercial applications. It integrates new phase sequence detection, phase loss protection, unbalance, and overload protection. With a three-phase current detection capability up to 200A and RS-485 communication, it allows for real-time remote monitoring.

Gambar 1: Hareupeun view of the Elitech CP-6000N Current Monitoring Relay, showing the digital display and control buttons.

Figure 2: Icons representing key features of the CP-6000N, including phase sequence, phase loss, unbalance, overload protection, 220A maximum current, RS-485 communication, and alarm function.
4. Fitur
- New phase sequence detection and protection design.
- Phase loss protection.
- Unbalance protection.
- Perlindungan beban.
- Three-phase current detection, with over-current protection up to 200A.
- Higher measurement accuracy: up to ±2A (0-30A).
- RS-485 communication function for remote monitoring of compressor running status.
- Current measurement range: 2-80A; 30-200A.
5. Spésifikasi
| Spésifikasi | Nilai |
|---|---|
| merek | Elitech |
| Modél | CP-6000N-SP-220V |
| Tipe Pamasangan | DIN Rail Gunung |
| Lampu tukang | Sumuhun |
| Tipe Panyambung | sekrup |
| Bahan Kontak | pérak |
| Tipe Kontak | Biasana Ditutup |
| Peunteun ayeuna | 200 Amps |
| Modeu Operasi | Otomatis |
| Sertifikasi | CE, UL |
| UPC | 781454242306 |
6. Setup jeung Instalasi
6.1 Pamasangan
The Elitech CP-6000N is designed for DIN Rail mounting. Ensure the DIN rail is securely installed in a suitable enclosure, providing adequate ventilation and protection from environmental factors.

Figure 3: Mounting dimensions of the CP-6000N, indicating a width of 2.8 inches and a height of 1.14 inches.
6.2 Diagram Wiring
Follow the wiring diagram carefully to ensure correct power supply, current sensor connections, and RS-485 communication. Incorrect wiring can lead to malfunction or damage.

Figure 4: Wiring diagram for the CP-6000N, showing terminals for Alarm, Power (W, V, U, N), Current Sensor (COM, A, B, C), and RS-485 (B-, A+).
Katerangan terminal:
- 1-2: Alarm output contacts.
- 3-6 (W, V, U, N): Three-phase power input.
- 7 (KOM): Common terminal for current sensors.
- 8-10 (A, B, C): Current sensor inputs for phases A, B, and C.
- 11-12 (B-, A+): RS-485 communication terminals.
7. Parentah Operasi
7.1 Operasi Dasar
The CP-6000N features a digital display and several buttons for configuration and monitoring.

Figure 5: A hand interacting with the control buttons of the CP-6000N, highlighting ease of use.
- Setél/View Tombol: Press to enter parameter setting mode or view parameter béda.
- Esc Button: Press to exit the current menu or cancel an operation.
- Panah luhur/handap: Use to navigate through menu options or adjust parameter values.
7.2 Current Monitoring
The device continuously monitors the three-phase current. The current measurement range is 2-80A or 30-200A, depending on the specific model variant. The digital display shows the measured current values.
7.3 RS-485 Komunikasi
The integrated RS-485 communication function allows the CP-6000N to be connected to a network for remote monitoring. This enables real-time tracking of compressor status and other operational data. Refer to the RS-485 communication protocol document for detailed integration instructions.
8. Pangropéa
The Elitech CP-6000N is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.
- Inspeksi Visual: Regularly inspect the device for any signs of physical damage, loose connections, or overheating.
- beberesih: Keep the device clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use liquid cleaners.
- Cék sambungan: Periodically verify that all wiring connections are secure.
9. Cara ngungkulan
If the CP-6000N exhibits unexpected behavior or displays fault codes, refer to the following information.

Figure 6: Table of fault codes and their meanings for the CP-6000N.
| No. | Kode Kasalahan | Hartina |
|---|---|---|
| 1 | EPS | Kasalahan runtuyan fase |
| 2 | EPL | Perlindungan fase leungitna |
| 3 | EoL | panyalindungan overload |
| 4 | EUb | panyalindungan unbalance |
Tip Umum pikeun Ngatasi Masalah:
- Henteu aya kakuatan: Check power supply connections and circuit breakers.
- Bacaan anu salah: Verify current sensor connections and calibration settings.
- Masalah Komunikasi: Check RS-485 wiring, baud rate, and address settings.
10. Garansi jeung Rojongan
Elitech products are manufactured to high-quality standards and are backed by a manufacturer's warranty. For specific warranty terms and conditions, please refer to the warranty card included with your product or visit the official Elitech websitus.
For technical support, troubleshooting assistance, or service inquiries, please contact Elitech customer service through their official websitus atawa inpo kontak disadiakeun kalawan pameseran Anjeun.