Brainchild E62 PID Temperature Controller

Brainchild-E62-PID-Temperature-Controller- product

Leuwihview & Appearance

Brainchild-E62-PID-Temperature-Controller- (2)

Kenop sareng Pintonan

OPERASI KEYPAD

Konci Gulung: Brainchild-E62-PID-Temperature-Controller- (3)
This key is used to select a parameter to be viewed atanapi disaluyukeun.

UP/Increase KEY:Brainchild-E62-PID-Temperature-Controller- (4)
Konci ieu dianggo pikeun ningkatkeun nilai parameter anu dipilih.

DOWN/Decrease KEY:  Brainchild-E62-PID-Temperature-Controller- (5)
Konci ieu dianggo pikeun nurunkeun nilai parameter anu dipilih.

SHIFT KEY:Brainchild-E62-PID-Temperature-Controller- (6)
konci ieu dipaké pikeun:

  • Move to the digit of the selected parameter and change the value by using up or down key to increase or decrease the value.

Gulung ka luhur: Brainchild-E62-PID-Temperature-Controller- (7)
Two keys pressed synchronously are used to:

  • Go to the previous parameter

RESET: + Brainchild-E62-PID-Temperature-Controller- (8)
Two keys pressed synchronously are used to:

  • Balikkeun tampilan ka layar utama.
  • Reset alarm latching sawaktos kondisi alarm dicabut.
  • Ngeureunkeun mode kontrol manual, mode Auto-Tuning atawa mode calibration.
  • Hapus hiji Auto-Tuning atawa pesen kasalahan komunikasi.
  • Enter the manual control menu if a failure mode occurs.

Gulung ka handap: Brainchild-E62-PID-Temperature-Controller- (9)
Two keys pressed synchronously directly go to the Manual control mode

Asupkeun konci: Brainchild-E62-PID-Temperature-Controller- (3)
Pencét Brainchild-E62-PID-Temperature-Controller- (3) jeung tahan salila 5 detik atawa leuwih panjang pikeun:

  • Enter the Auto-Tuning mode. Brainchild-E62-PID-Temperature-Controller- (10) Pintonan bakal nunjukkeun.
  • Enter the manual control mode. Brainchild-E62-PID-Temperature-Controller- (11) Pintonan bakal nunjukkeun.
    Enter the setup menu mode. Brainchild-E62-PID-Temperature-Controller- (12)Pintonan bakal nunjukkeun.
  • Brainchild-E62-PID-Temperature-Controller- (13) Perform calibration of a selected parameter during the calibration procedure. The display will show

Bagan alur menu

Menu geus dibagi kana 5 grup. Aranjeunna kieu:

  1. Menu Panganggo
  2. Auto-Tuning Mode Menu
  3. Menu Mode Manual
  4. Setup Menu
  5. Calibration Mode Menu

Brainchild-E62-PID-Temperature-Controller- (14)

  • Pencét Brainchild-E62-PID-Temperature-Controller- (3) for the next parameter ; Press Brainchild-E62-PID-Temperature-Controller- (3) jeung Brainchild-E62-PID-Temperature-Controller- (4) konci pikeun mulang ka parameter saméméhna.
  • Pencét jeung tahanBrainchild-E62-PID-Temperature-Controller- (3) for 3.1 seconds, then let go to select auto tuning mode.
  • Pencét jeung tahan Brainchild-E62-PID-Temperature-Controller- (3)for 4.2 seconds, then let go, to select manual control mode.
  • Pencét jeung tahan Brainchild-E62-PID-Temperature-Controller- (3)for 5.3 seconds, then let go to select setup mode.
  • Pencét jeung tahan Brainchild-E62-PID-Temperature-Controller- (3) salila 6.4 detik, lajeng hayu balik pikeun milih mode calibration.

Menu Panganggo
Paké Brainchild-E62-PID-Temperature-Controller- (3) key to enter basic menu parameters, and press  Brainchild-E62-PID-Temperature-Controller- (3) again to select SP1, SEL1~SEL8.
Pencét  Brainchild-E62-PID-Temperature-Controller- (3)Brainchild-E62-PID-Temperature-Controller- (4) to return to the previous.

Brainchild-E62-PID-Temperature-Controller- (15)

Auto-Tuning Mode
Pencét Brainchild-E62-PID-Temperature-Controller- (3) key 5 seconds to activate Auto-Tuning Mode

Brainchild-E62-PID-Temperature-Controller- (16)

Menu Mode Manual
Pencét Brainchild-E62-PID-Temperature-Controller- (3) key 3 seconds to execute the selected default program

Brainchild-E62-PID-Temperature-Controller- (17)

Enter Manual Control Mode; refer to Manual 6.1 & 6.8.2~6.8.4

Brainchild-E62-PID-Temperature-Controller- (18)

Setup Menu
The setup menu has been categorized into eight categories.
They are listed as below.

  1. Menu Dasar (basis)
  2. Menu Kaluaran (kaluar)
  3. Communication Menu (CoMM)
  4. User Select Menu (SEL)

Menu Dasar (basis)
Paké Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get bASE in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to basic menu parameters.

Brainchild-E62-PID-Temperature-Controller- (19)

Menu Kaluaran (kaluar)
Paké Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get oUT in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to output menu parameters.

Brainchild-E62-PID-Temperature-Controller- (20)

Communication Menu (CoMM)
Paké Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get CoMM in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to communication menu parameters.
Please note that confirm A2FN set to CoMM when using communication.

Brainchild-E62-PID-Temperature-Controller- (21)

User Select Menu (SEL)
Paké Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key get SEL in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to select the user menu parameters.

Brainchild-E62-PID-Temperature-Controller- (22)

Modeu Kalibrasi

Brainchild-E62-PID-Temperature-Controller- (24)

Pencét Brainchild-E62-PID-Temperature-Controller- (3) key for 2 seconds or longer (not more than 3 seconds) ; then release it to enter calibration Mode.
Pencét Brainchild-E62-PID-Temperature-Controller- (3) key for 5 seconds to perform calibration

  • Please note that it is required to use specialized equipment to apply calibration, attempting to change will affect device accuracy

Catetan:

  • Using Manual, Auto-Tuning, Calibration modes will break the control loop and change some of the previous setting data. Make sure that the system is allowable to apply these modes.
  • The flow chart shows a complete list of all parameters. For actual application, the number of available parameters will vary depending on the setup and model of the controller and will be less than that shown in the flow chart.
  • The user can select up to 8 parameters to put in the user select menu by using the SEL1~SEL8 parameters in the setup menu

Before you Start, Setup Input/Output
After power-up, press and hold Brainchild-E62-PID-Temperature-Controller- (3) for 5.3 seconds, then let go to enter Setup Menu. Complete Parameter setting, INPT, UNIT, DP, O1TY, O1L and O1H.

  • Enter the Setup Menu. Press Brainchild-E62-PID-Temperature-Controller- (3) for 5 seconds to enter Basic Menu (bASE). Finish setting for INPT, UNIT and DP. Exit the level.
  •  Return to the Setup Menu. Press Brainchild-E62-PID-Temperature-Controller- (3) for 5 seconds to enter Output Menu (oUT). Finish setting for O1TY, O1L and O1H. Press and hold Brainchild-E62-PID-Temperature-Controller- (4) Brainchild-E62-PID-Temperature-Controller- (5)  and return to homepage.

Brainchild-E62-PID-Temperature-Controller- (25)

OP1L/ OP1H Table

Rentang OP1L OP1H
OM9A-3 4-20 20.0 100.0
OM9A-3 0-20 0.0 100.0
OM9A-5 0-5V 0.0 50.0
OM9A-5 1-5V 10.0 50.0
OM9A-5 0-10 0.0 100.0

* When O1TY as DC.MA or  DC. Vo, set the value based on usage requirement

Sambungan Terminal

Brainchild-E62-PID-Temperature-Controller- (1)

Notasi Parameter

User Menu Parameter

Modbus Parameter Katerangan Rentang Default Aksés
0 SP1 Set Point 1 Handap: SP1L

Luhur: SP1H

25.0 °C Urang Sunda/W
64 PV Nilai prosés Handap: -19999

Luhur: 45536

(77.0 °F) R
65 SV Current set point value Handap: SP1L

Luhur: SP1H

—— R
44  

SEL1

Select 1st parameter for user menu 0 Euweuh

1 A1SP

2 A2SP

3 KUNCI

4 INPT

5 PB

6 TI

7 TD

8 SHIF

9 OFST

10 O1HY

11 A1HY

12 A2HY

13 ADDR

—— Urang Sunda/W
45 SEL2 Select 2nd parameter Select 2nd parameter for user manual. Same as the SEL1 0 Urang Sunda/W
46 SEL3 Select 3rd parameter Select 3rd parameter for user manual. Same as the SEL1 0 Urang Sunda/W
47 SEL4 Select 4th parameter Select 4th parameter for user manual. Same as the SEL1 0 Urang Sunda/W
48 SEL5 Select 5th parameter Select 5th parameter for user manual. Same as the SEL1 0 Urang Sunda/W
49 SEL6 Select 6th parameter Select 6th parameter for user manual. Same as the SEL1 0 Urang Sunda/W
50 SEL7 Select 7th parameter Select 7th parameter for user manual. Same as the SEL1 0 Urang Sunda/W
51 SEL8 Select 8th parameter Select 8th parameter for user manual. Same as the SEL1 0 Urang Sunda/W

Manual Mode Parameter

Modbus Parameter Katerangan Rentang Default Aksés
66 MV1 Output 1 %Value Handap: 0.00

Luhur: 100.00%

—– R (R/W,

manual)

Basic (bASE) Parameter

Modbus Parameter Katerangan Rentang Default Aksés
3 KUNCI Select parameters to be locked 0 None: No parameter is locked

1  SEt: Setup data are locked

2 uSEr: Setup data and user data are locked. SetPoint are unlocked.

3  ALL: All data are locked

0 Urang Sunda/W
4 INPT Input sensor selec- tion 0 J_tC: J tipe Thermocouple

1 K_tC: K tipe Thermocouple

2 t_tC: T type Thermocouple

3 R_tC: R tipe Thermocouple

4 S_tC: S type Thermocouple

5 Pt. dN: PT 100 DIN

6 Pt.JS: PT 100 JIS

1 Urang Sunda/W
5 UNIT Pilihan unit input 0 oC: °C unit

1 oF: °F unit

0 Urang Sunda/W
6 DP Decimal point selec- tion 0 No.dP: no decimal point

1 1-dP: 1 decimal point

 

1

 

Urang Sunda/W

 

9

 

SP1L

Low limit of set point value rendah:

J_TC: -120.0°C (-184.0°F)

K_TC: -200.0°C (-328.0°F)

T_TC: -250.0°C (-418.0°F) R_TC: 0.0°C ( 32.0°F) S_TC: 0.0°C ( 32.0°F) PTDN: -200.0°C (-328.0°F)

PTJS: -200.0°C (-328.0°F)

Luhur: SP1H

-17.8 °C

(0.0 °F)

 

Urang Sunda/W

10  

SP1H

High limit of set point value Handap: SP1L

luhur:

J_TC: 1000.0°C (1828.0°F) K_TC: 1370.0°C (2498.0°F) T_TC: 400.0°C ( 752.0°F) R_TC: 1767.7°C (3214.0°F) S_TC: 1767.7°C (3214.0°F) PTDN: 850.0°C (1562.0°F) PTJS: 600.0°C (1112.0°F)

537.8 °C

(1000.0 °F)

 

Urang Sunda/W

12 FILT  

Nyaring damping time constant of PV

0 0: 0 sec time constant

1 0.2: 0.2 sec time constant

2 0.5: 0.5 sec time constant

3 1: 1 sec time constant

4 2: 2 sec time constant

5 15: 5 sec time constant

6 10: 10 sec time constant

7 20: 20 sec time constant

8 30: 30 sec time constant

9 60: 60 sec time constant

2 Urang Sunda/W
14 PB Band proporsional

nilai

Handap: 0.0

Luhur: 500.0°C (900.0°F)

10.0 °C

(18.0 °F)

Urang Sunda/W
15 TI Nilai waktos integral Low: 0, High: 3600 sec 60 Urang Sunda/W
16 TD Nilai waktos turunan Low: 0, High: 360.0 sec 30.0 Urang Sunda/W
11 SHIF PV shift (offset)

nilai

Low: -200.0°C (-360.0°F) High: 200.0°C (360.0°F) 0.0 °C

(0.0 °F)

Urang Sunda/W
68 CICF CIC filter switch 0 OFF

1 DINA

0 R

Output (oUT) Parameter

Modbus Parameter Katerangan Rentang Default Aksés
17 OUT1 Kaluaran 1 fungsi 0 REVR: Reverse (heating) control action

1 dIRt: Direct (cooling) control action

0 Urang Sunda/W
21 CYC1 Kaluaran 1 waktos siklus Low: 0.1;

Luhur: 90.0 detik.

18.0 Urang Sunda/W
18 O1TY Kaluaran 1 tipe sinyal 0 RELY: kaluaran relay

1 SSrd: Kaluaran drive relay kaayaan padet

2 DC.MA: DC current

3 DC.Vo: DC voltage

0 Urang Sunda/W
7 OP1L OP1 linear output low limit value 0.0 ~ OP1H 0.0 Urang Sunda/W
8 OP1H OP1 linear output

nilai wates luhur

OP1L ~ 110.0 % 100.0 Urang Sunda/W
19 O1FT Kaluaran 1 modeu transfer gagal 0~1000: 0.0 ~ 100.0 % to continue output 1

control function if the sensor fails, or select OFF (0) or ON (1) for ON-OFF control

0.0 Urang Sunda/W
22 OFST Offset value for P

kadali

Handap: 0

Luhur: 100.0%

25.0 Urang Sunda/W
20 O1 HY Output 1 ON-OFF

control hysteresis

Handap: 0.1

High: 50.0 °C (90.0°F)

0.5 °C

(0.9 °F)

Urang Sunda/W
23 PL1L MV1 power value

limit low

Handap: 0

High: 50 % or PL1H

0 Urang Sunda/W
24 PL1H MV2 power value limit high Handap: PL1L

Luhur: 100%

 

100

 

Urang Sunda/W

25 A1FN Alarm 1 function for alarm 1 output 0 NoNE: No alarm function

1 dE.HI: Deviation high alarm

2 dE.Lo: Deviation low alarm

3 db.HI: Deviation band out of band alarm

4 db.Lo: Deviation band in band alarm

5 PV.HI: Process value high alarm

6 PV.Lo: Process value low alarm

 

1

 

Urang Sunda/W

Modbus Parameter Katerangan Rentang Default Aksés
 

26

 

A1MD

 

Alarm 1 operation mode

0 NoRM: Normal alarm action

1 LtCH: Latching alarm action

2 HoLd: Hold alarm action

3 Lt.Ho: Latching & Hold action

0 Urang Sunda/W
29 A1HY Alarm 1 Hysteresis control Handap: 0.1

Luhur: 50.0°C (90.0°F)

0.1 °C

(0.2 °F)

Urang Sunda/W
34 A1DL Alarm 1 delay Low: 0; High: 5999 sec 0 Urang Sunda/W
28 A1FT Alarm 1 failure trans- fer mode 0 oFF: OFF if sensor fails

1 oN: ON if sensor fails

1 Urang Sunda/W
1 A1SP Alarm 1 set point A1FN=PVHI/PVLO

Low: SP1L High: SP1H

100.0 °C

(212.0 °F)

Urang Sunda/W
13 A1DV Alarm 1 deviation value A1FN=DEHI/DELO/DBHI/DBLO

Low: 0.0 High: 500.0°C (900.0°F)

10.0 °C

(18.0 °F)

Urang Sunda/W
33  

A2FN

 

Alarm 2 function for alarm 2 output

0 NoNE: No alarm function

1 dE.HI: Deviation high alarm

2 dE.Lo: Deviation low alarm

3 db.HI: Deviation band out of band alarm

4 db.Lo: Deviation band in band alarm

5 PV.HI: Process value high alarm

6 PV.Lo: Process value low alarm

7 COMM: RS485

 

2

Urang Sunda/W
 

35

 

A2MD

 

Alarm 2 operation mode

0 NoRM: Normal alarm action

1 LtCH: Latching alarm action

2 HoLd: Hold alarm action

3 Lt.Ho: Latching & Hold action

 

0

 

Urang Sunda/W

36 A2HY Hysteresis control of alarm 2 Handap: 0.1°C

Luhur: 50.0°C (90.0°F)

0.1 °C

(0.2 °F)

Urang Sunda/W
38 A2DL Alarm 2 delay Low: 0; High: 5999 sec 0 Urang Sunda/W
37 A2FT Alarm 2 failure forced transfer mode 0 oFF: Alarm output OFF if sensor fails

1 oN: Alarm output ON if sensor fails

1 Urang Sunda/W
2 A2SP Alarm 2 set point A2FN=PVHI/PVLO

Low: SP1L High: SP1H

100.0 °C

(212.0 °F)

Urang Sunda/W
43 A2DV Alarm 2 deviation value A2FN=DEHI/DELO/DBHI/DBLO

Low: 0.0 High: 500.0°C (900.0°F)

10.0 °C

(18.0 °F)

Urang Sunda/W

Communication (CoMM) Parameter

Modbus Parameter Katerangan Rentang Default Aksés
39 ADDR Address assignment of digital
komunikasi
Handap: 1

Luhur: 255

1 Urang Sunda/W
40 BAUD Baud rate of digital communication 0   2.4: 2.4 Kbits/s baud rate

1   4.8: 4.8 Kbits/s baud rate

2   9.6: 9.6 Kbits/s baud rate

3  14.4: 14.4 Kbits/s baud rate

4  19.2: 19.2 Kbits/s baud rate

5  28.8: 28.8 Kbits/s baud rate

6  38.4: 38.4 Kbits/s baud rate

7  57.6: 57.6 Kbits/s baud rate

8  115.2: 115.2 Kbits/s baud rate

2 Urang Sunda/W
41 DATA Data bit count of dig- ital communication 0 7bIt: 7 bit

1 8bIt: 8 bit

1 Urang Sunda/W
42 PARI The parity bit of digi- tal communication 0 EVEN: Even parity

1  odd: Odd parity

2 NoNE: No parity bit

 

0

 

Urang Sunda/W

Calibration Mode Parameter

Modbus Parameter Katerangan Rentang Default Aksés
52 ADLO mV calibration low

koefisien

Handap: -1999

Luhur: 1999

 

—–

 

Urang Sunda/W

53 ADHI mV calibration high

koefisien

Handap: -1999

Luhur: 1999

 

—–

 

Urang Sunda/W

54 RTDL RTD calibration low

koefisien

Handap: -1999

Luhur: 1999

 

—–

 

Urang Sunda/W

55 RTDH RTD calibration high coefficient Handap: -1999

Luhur: 1999

 

—–

 

Urang Sunda/W

56 CJLO Cold junction calibra-

tion low coefficient

Handap: -5.00

Luhur: 40.00

 

—–

 

Urang Sunda/W

Parameter séjén

Modbus Parameter Katerangan Rentang Default Aksés
57 CJCT Suhu simpang tiis Handap: -4000

Luhur: 9000

—– R
58 TANGGAL titimangsa Low: 0;

Luhur: 65535

—– R
59 SRNO Nomer séri Low: 0;

Luhur: 65535

—– R
63 CJCL Cold junction low calibration

voltage

Handap: 0

Luhur: 7552

—– R
69 EROR Kode kasalahan Low: 0; High: 65535 —– R
70 MODÉ Operation mode & alarm status Handap: 0

Luhur: 65535

—– R
71 PROG Device version, firmware version 67.XX —– R
72 KTP Kode paréntah Low: 0; High: 65535 —– Urang Sunda/W
73 JOB1 Job code Low: 0; High: 65535 —– Urang Sunda/W

Kode Kasalahan

Kasalahan Kodeu tampilan

Lambang

 

Katerangan & Alesan

 

Koréksi Aksi

10 ER10 Kasalahan komunikasi: kode fungsi goréng Correct the communication software to meet the protocol

syarat

11 ER11 Kasalahan komunikasi: ngadaptarkeun alamat di luar jangkauan Do not issue an over-range address of the register to the slave
14 ER14 Communication error: attempt to write a

read-only data

Do not write read-only data or protected data to the slave
15 ER15 Kasalahan komunikasi: nyerat nilai anu di luar jangkauan pikeun ngadaptar Do not write an over-range data to the slave register
26 ATER Auto-Tuning Error: Failed to perform Auto-Tuning function
  1. The PID values obtained after Auto-Tuning process are out of
    range. Retry Auto-Tuning.
    Auto-Tuning process exceeds 3600 secs
  2. Do not change the setpoint value during Auto-Tuning process.
  3. Use manual tuning instead of Auto-Tuning process.
  4.  Do not set the value as zero for TI & PB.
29 EEPR EEPROM teu tiasa ditulis leres Balik deui ka produsén pikeun perbaikan.
30 CJER santunan simpang tiis pikeun

Thermocouple malfungsi

Balik deui ka produsén pikeun perbaikan.
39 SBER Input sensor break Replace the input sensor
40 ADER A to D converter atawa komponén patali (s) gangguan Return to the original manufacturer for repair.

FAQ

How do I access the User Menu?

To access the User Menu, press the corresponding key on the controller.

How do I activate Auto-Tuning Mode?

To activate Auto-Tuning Mode, press and hold a specific key for 5 seconds.

How do I enter Manual Control Mode? To enter Manual Control Mode, press the designated key for 3 seconds. How do I perform calibration? To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.

To enter Manual Control Mode, press the designated key for 3 seconds.

How do I perform calibration?

To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.