iSMACONTROLLI SFAR-S-6TI Modbus IO Module

SPESIFIKASI
| Sasayogian tanaga | Voltage | 10-38 V DC; 10-28 V AC |
| Konsumsi kakuatan | 2,4 W @ 24 V DC 3 VA @ 24 V AC | |
| Input suhu | 6x Résistif atanapi thermocouple tiasa dikonfigurasi, résolusi 0,1 ° C | |
| Kaluaran digital | 2xTransistor kaluaran max 55 V DC, max 500 mA | |
| Isolasi Galvanik | Max 1500 Vrms | |
| Panganteur | RS485, nepi ka 128 alat dina beus | |
| Baudrat | Ti 2400 nepi ka 115200 bps | |
| Perlindungan ingress | IP40 – pikeun instalasi jero rohangan | |
| Suhu | Operasi -10°C – +50°C; Panyimpenan -40°C – +85°C | |
| Kalembaban relatif | 5 nepi ka 95% RH (tanpa kondensasi) | |
| Panyambung | Max 2.5 mm2 | |
| Diménsi | 119,1 mm x 101 mm x 22,6 mm | |
| Pamasangan | Pamasangan rel DIN (DIN EN 50022) | |
| Bahan perumahan | palastik, PC / ABS timer extinguishing | |
PANEL TOP

INPUT SUHU

KOMUNIKASI kakuatan suplai


SASAYOGIAN TANAGA

PERHATOSAN 
- Catet, kabel anu salah tina produk ieu tiasa ngaruksak sareng ngakibatkeun bahaya anu sanés. Pastikeun produk geus bener kabel samemeh ngahurungkeun kakuatan ON.
- Sateuacan kabel, atanapi nyabut/masang produk, pastikeun mareuman kakuatan. Gagal pikeun ngalakukeunana tiasa nyababkeun shock listrik.
- Ulah noél bagian nu boga muatan listrik saperti terminal kakuatan. Jang ngalampahkeun kitu bisa ngabalukarkeun shock listrik.
- Ulah ngabongkar produk. Lakukeun kitu bisa ngabalukarkeun shock listrik atawa operasi faulty.
- Anggo produk dina rentang operasi anu disarankeun dina spésifikasi (suhu, kalembaban, voltage, shock, ningkatna arah, atmosfir jsb). Gagal pikeun ngalakukeunana tiasa nyababkeun seuneu atanapi operasi anu salah.
- Pageuh tighten kawat ka terminal. Teu cukup tightening tina kawat ka terminal bisa ngabalukarkeun seuneu.
TERMINAL alat

| Modbus | Dec | Hex | Ngadaptar Ngaran | Aksés | Katerangan | |||
| 30001 | 0 | 0x00 | Vérsi / Tipe | Maca | Vérsi sareng Jenis alat | |||
| 30002 | 1 | 0x01 | Saklar | Maca | Ngalihkeun kaayaan | |||
| 40003 | 2 | 0x02 | Laju baud | Maca & Nulis | Laju baud RS485 | |||
| 40004 | 3 | 0x03 | Eureun Bits & Data Bits | Maca & Nulis | No of Stop bit & Data Bits | |||
| 40005 | 4 | 0x04 | Paritas | Maca & Nulis | Parity bit | |||
| 40006 | 5 | 0x05 | Tunda Tanggapan | Maca & Nulis | Tunda réspon dina ms | |||
| 40007 | 6 | 0x06 | Modbus Mode | Maca & Nulis | Modbus Mode (ASCII atanapi RTU) | |||
| 40010 | 9 | 0x09 | Saringan analog | Maca & Nulis | Konfigurasi nyaring analog | |||
| 40033 | 32 | 0x20 | Nampa pakét LSR (Reg. Least Significant) | Maca & Nulis | Jumlah pakét nampi | |||
| 40034 | 33 | 0x21 | Nampi pakét MSR (Paling Signifikan Reg.) |
Maca & Nulis |
||||
| 40035 | 34 | 0x22 | pakét LSR salah | Maca & Nulis |
Henteu aya pakét anu ditampi kalayan kasalahan |
|||
| 40036 | 35 | 0x23 | pakét MSR salah | Maca & Nulis | ||||
| 40037 | 36 | 0x24 | Dikirim pakét LSR | Maca & Nulis |
Henteu aya pakét anu dikirim |
|||
| 40038 | 37 | 0x25 | Dikirim pakét MSR | Maca & Nulis | ||||
|
30051 |
50 |
0x32 |
Input |
Maca |
sensor disambungkeun
Bit dina kaayaan luhur → sensor disambungkeun |
|||
| 40052 | 51 | 0x33 | Kaluaran | Maca & Nulis | Alarm kaayaan bit 6 jeung 7 kaluaran alarem | |||
| 30053 | 52 | 0x34 | Suhu 1 | Maca | Suhu atawa analog diukur dina mV·10 pikeun voltage ka 2048 mV dina mV · 100 pikeun voltage ka 256 mV dina °C·10 pikeun suhu
dina Ω pikeun lalawanan |
|||
| 30054 | 53 | 0x35 | Suhu 2 | Maca | ||||
| 30055 | 54 | 0x36 | Suhu 3 | Maca | ||||
| 30056 | 55 | 0x37 | Suhu 4 | Maca | ||||
| 30057 | 56 | 0x38 | Suhu 5 | Maca | ||||
| 30058 | 57 | 0x39 | Suhu 6 | Maca | ||||
|
30059 |
58 |
0x3A |
Suhu alarem 1 |
Maca |
Suhu alarem pikeun kaluaran alarem 1 | |||
|
30060 |
59 |
0x3B |
Suhu alarem 2 |
Maca |
Suhu alarem pikeun kaluaran alarem 2 | |||
| 30061 | 60 | 0 x 3C | Suhu simpang | Maca | Suhu simpang modul | |||
| 30062 | 61 | 0x3D | Pangukuran ayeuna | Maca | Pangukuran ayeuna | |||
| 40063 | 62 | 0x3E | MAX tingkat alarem 1 | Maca & Nulis |
Upami suhu ngaleuwihan nilai ieu, bendera alarm anu saluyu disetel |
|||
| 40064 | 63 | 0x3f | MAX tingkat alarem 2 | Maca & Nulis | ||||
| 40065 | 64 | 0x40 | MAX tingkat alarem 3 | Maca & Nulis | ||||
| 40066 | 65 | 0x41 | MAX tingkat alarem 4 | Maca & Nulis | ||||
| 40067 | 66 | 0x42 | MAX tingkat alarem 5 | Maca & Nulis | ||||
| 40068 | 67 | 0x43 | MAX tingkat alarem 6 | Maca & Nulis | ||||
| 40069 | 68 | 0x44 | MIN tingkat alarem 1 | Maca & Nulis |
Lamun hawa handap nilai ieu pakait bendera alarm disetel |
|||
| 40070 | 69 | 0x45 | MIN tingkat alarem 2 | Maca & Nulis | ||||
| 40071 | 70 | 0x46 | MIN tingkat alarem 3 | Maca & Nulis | ||||
| 40072 | 71 | 0x47 | MIN tingkat alarem 4 | Maca & Nulis | ||||
| 40073 | 72 | 0x48 | MIN tingkat alarem 5 | Maca & Nulis | ||||
| 40074 | 73 | 0x49 | MIN tingkat alarem 6 | Maca & Nulis | ||||
| 40075 | 74 | 0x4A | Setélan alarem 1 | Maca & Nulis | Setélan alarem 0 - alarem alatan suhu ayeuna 1 - Inget nilai alarem, dugi reset ku master via Modbus |
|||
| 40076 | 75 | 0x4B | Setélan alarem 2 | Maca & Nulis | ||||
| 40077 | 76 | 0 x 4C | Setélan alarem 3 | Maca & Nulis | ||||
| 40078 | 77 | 0x4D | Setélan alarem 4 | Maca & Nulis | ||||
| 40079 | 78 | 0x4E | Setélan alarem 5 | Maca & Nulis | ||||
| 40080 | 79 | 0x4f | Setélan alarem 6 | Maca & Nulis | ||||
| 40081 | 80 | 0x50 | simpang konstan | Maca & Nulis | Nilai suhu simpang | |||
| 40082 | 81 | 0x51 | Suhu simpang | Maca & Nulis | Suhu simpang offset | |||
| 40083 | 82 | 0x52 | Input 1 setélan | Maca & Nulis | Modeu input analog:
0 - input ditumpurkeun 1 – voltage ka 2048 mV 2 – voltage ka 256 mV 3 - J thermocouple 4 – K thermocouple 5 – T thermocouple 6 – N thermocouple 7 – S thermocouple |
|||
| 40084 | 83 | 0x53 | Input 2 setélan | Maca & Nulis | ||||
| 40085 | 84 | 0x54 | Input 3 setélan | Maca & Nulis | ||||
| 40086 | 85 | 0x55 | Input 4 setélan | Maca & Nulis | ||||
| 40087 | 86 | 0x56 | Input 5 setélan | Maca & Nulis | ||||
| 40088 | 87 | 0x57 | Input 6 setélan | Maca & Nulis | ||||
| 40089 | 88 | 0x58 | Kaluaran 1 setélan | Maca & Nulis | Setélan kaluaran alarem 0 - kaluaran diatur ku PLC
+1 - suhu ti input 1 +2 - suhu ti input 2 +4 - suhu ti input 3 +512 - Kaluaran disetel upami nilaina kirang ti Nilai Alarm (register 40091 atanapi 40092) ("pemanasan") +1024 - Nilai panghandapna tina inputs dipilih +2048 - Nilai greatest ti inputs dipilih (upami henteu milih salah sahiji tina dua pilihan di luhur tibatan anu dianggo nilai rata-rata input anu dipilih) |
|||
| 40090 | 89 | 0x59 | Kaluaran 2 setélan | Maca & Nulis | ||||
| 40091 | 90 | 0x5A | Nilai Alarm 1 | Maca & Nulis | nilai alarem pikeun outputs | |||
| 40092 | 91 | 0x5B | Nilai Alarm 2 | Maca & Nulis | ||||
| 40093 | 92 | 0 x 5C | Histeresis alarem 1 | Maca & Nulis | Nilai histeresis pikeun kaluaran alarem | |||
| 40094 | 93 | 0x5D | Histeresis alarem 2 | Maca & Nulis | ||||
| 40095 | 94 | 0x5E | Résistansi input 1 | Maca & Nulis |
Lalawanan kawat kalungguhan pikeun tiap input |
|||
| 40096 | 95 | 0x5f | Résistansi input 2 | Maca & Nulis | ||||
| 40097 | 96 | 0x60 | Résistansi input 3 | Maca & Nulis | ||||
| 40098 | 97 | 0x61 | Résistansi input 4 | Maca & Nulis | ||||
| 40099 | 98 | 0x62 | Résistansi input 5 | Maca & Nulis | ||||
| 40100 | 99 | 0x63 | Résistansi input 6 | Maca & Nulis | ||||
PEDOMAN INSTALASI
Mangga baca parentah saméméh ngagunakeun atawa ngoperasikeun alat. Upami aya patarosan saatos maca dokumén ieu, mangga ngahubungi Tim Dukungan iSMA CONTROLLI
(support@ismacontrolli.com).
Sateuacan masang kabel atanapi nyabut/masang produk, pastikeun mareuman kakuatan. Gagal pikeun ngalakukeunana tiasa nyababkeun shock listrik.- Kabel produk anu teu leres tiasa ngaruksak sareng ngakibatkeun bahaya anu sanés. Pastikeun yén produk geus bener kabel samemeh ngahurungkeun daya.
- Ulah noél bagian nu boga muatan listrik kayaning terminal kakuatan. Ngalakukeunana tiasa nyababkeun shock listrik.
- Ulah ngabongkar produk. Lakukeun kitu bisa ngabalukarkeun shock listrik atawa operasi faulty
Anggo produk ngan ukur dina rentang operasi anu disarankeun dina spésifikasi (suhu, kalembaban, voltage, shock, ningkatna arah, atmosfir, jsb). Gagal pikeun ngalakukeunana tiasa nyababkeun kahuruan atanapi operasi anu salah.- Hindarkeun masang produk dina jarak anu caket sareng alat sareng kabel listrik kakuatan tinggi, beban induktif, sareng alat gentos. Deukeutna objék sapertos kitu tiasa nyababkeun gangguan anu teu terkendali, nyababkeun operasi produk anu teu stabil.
- Susunan kakuatan sareng kabel sinyal anu leres mangaruhan operasi sadaya sistem kontrol. Hindarkeun nempatkeun kakuatan sareng kabel sinyal dina baki kabel paralel. Éta tiasa nyababkeun gangguan dina sinyal anu diawaskeun sareng kontrol.
- Disarankeun pikeun kakuatan Controllers / modul jeung suppliers kakuatan AC / DC. Aranjeunna nyayogikeun insulasi anu langkung saé sareng langkung stabil pikeun alat dibandingkeun sareng sistem trafo AC / AC, anu ngirimkeun gangguan sareng fenomena fana sapertos lonjakan sareng ledakan kana alat. Éta ogé ngasingkeun produk tina fenomena induktif tina trafo sareng beban sanés.
- Sistim catu daya pikeun produk kudu ditangtayungan ku alat éksternal ngawatesan overvoltage sarta épék discharges kilat.
- Hindarkeun kakuatan produk sareng alat anu dikontrol/diawaskeun, khususna kakuatan anu luhur sareng beban induktif, tina hiji sumber listrik. Alat kakuatan tina sumber kakuatan tunggal ngabalukarkeun résiko gangguan tina beban ka alat kontrol.
- Upami trafo AC / AC dianggo pikeun nyayogikeun alat kontrol, disarankeun pisan nganggo trafo 100 VA Kelas 2 maksimal pikeun nyegah épék induktif anu teu dihoyongkeun, anu bahaya pikeun alat.
- Garis pangawas sareng kontrol anu panjang tiasa nyababkeun puteran dina sambungan sareng catu daya anu dibagikeun, nyababkeun gangguan dina operasi alat, kalebet komunikasi éksternal. Disarankeun ngagunakeun separator galvanic.
- Pikeun nangtayungan jalur sinyal jeung komunikasi ngalawan gangguan éléktromagnétik éksternal, ngagunakeun kabel shielded grounded leres tur manik ferrite.
- Ngalihkeun relay kaluaran digital tina beban induktif anu ageung (ngaleuwihan spésifikasi) tiasa nyababkeun gangguan pulsa kana éléktronika anu dipasang di jero produk. Ku alatan éta, disarankeun pikeun ngagunakeun relay éksternal / kontaktor, jsb pikeun pindah beban sapertos. Pamakéan controller kalawan outputs triac ogé ngawatesan overvol sarupatage fenomena.
- Seueur kasus gangguan sareng overvoltage dina sistem kontrol dihasilkeun ku switched, beban induktif disadiakeun ku vol mains bolaktage (AC 120/230 V). Upami aranjeunna henteu ngagaduhan sirkuit pangurangan bising anu diwangun, disarankeun pikeun nganggo sirkuit éksternal sapertos snubber, varistor, atanapi dioda panyalindungan pikeun ngawatesan épék ieu.
Pamasangan listrik produk ieu kedah dilakukeun saluyu sareng kode kabel nasional sareng saluyu sareng peraturan lokal.
iSMA CONTROLLI SpA - Via Carlo Levi 52, 16010 Sant'Olcese (GE) - Italia | support@ismacontrolli.com
www.ismacontrolli.com
Pituduh Pamasangan| 1
st Ngaluarkeun rev. 1 | 05/2022
![]()

Dokumén / Sumberdaya
![]() |
iSMACONTROLLI SFAR-S-6TI Modbus IO Module [pdf] Instruksi Manual SFAR-S-6TI Modbus IO Module, SFAR-S-6TI, Modbus IO Module, IO Module, Module |