TERACOM TDO340 Modbus RTU Relay Kaluaran Module

FAQs
- Q: Naon anu kudu dipigawé lamun kuring kudu pindah vol bahayatages ngagunakeun alat?
- A: Lamun perlu pindah vol bahayatages (leuwih 30V), jalma terampil kudu masang alat dina kamar kalawan aksés dikawasa sakumaha per tungtunan kaamanan.
pedaran pondok
Modul kaluaran relay MODBUS RTU, modél TDO340, mangrupikeun alat SPST 4 saluran anu tiasa diandelkeun sareng gaduh kontak mandiri. Éta ngadukung sapinuhna protokol MODBUS RTU, ngamungkinkeun anjeun ngonpigurasikeun status kaamanan relay boh dina ngamimitian sareng upami aya leungitna komunikasi, mastikeun panyalindungan sistem terus. Modul ieu dilengkepan fungsi panjaga anu ngadeteksi gagal komunikasi sareng nyandak tindakan gancang pikeun ngajaga kaamanan. Salaku tambahan, TDO340 ngagunakeun mémori nonvolatile pikeun nahan sareng malikkeun kaayaan relay saatos kakuatan.tages. Alat ieu tiasa dianggo salaku ekstensi kaluaran relay pikeun alat master MODBUS RTU.
Fitur
- panganteur RS-485 ngarojong nepi ka 63 titik
- memori non-volatile pikeun status relays '
- Indikator LED pikeun status komunikasi
- fungsionalitas Watchdog pikeun leungitna komunikasi
- Isolasi bertulang tina kontak relay
- Diwangun-di 120 ohm résistor terminasi
- DIN ningkatna rel
- Update firmware via panganteur
Aplikasi
- Konsumén AC / DC commutation;
- Kontrol prosés industri;
spésifikasi
- Ciri fisik
- Diménsi: 52x91x59mm (3-modul enclosure)
- Beurat: 101g
- Pamasangan: Dina 35 mm DIN top-hat rail
- Watesan lingkungan
- Kisaran suhu operasi: -20 nepi ka 60°C
- Operasi rentang asor relatif: 10 nepi ka 90% (non-condensing)
- Kisaran suhu panyimpenan: -25 nepi ka 65 ° C
- Panyimpenan rentang kalembaban relatif: 5 nepi ka 95% (non-condensing)
- Perlindungan ingress: IP40 (sambungan IP20)
- Sasayogian tanaga
- Operasi voltage rentang (kaasup -15/+20% nurutkeun IEC 62368-1): 5 mun 28VDC konsumsi Ayeuna: 130mA @ 5V
- Kaluaran relay
- Arus switching maksimum: 3A
- Maksimum switching AC voltage: 250v
- Maksimum switching DC voltage: 30v
- beban dipeunteun: 3A di 250VAC, résistif, 50k siklus
- 3A dina 30VDC, résistif, 30k siklus
- Isolasi: 4000 Vrms coil pikeun kontak
- 1000 Vrms antara kontak kabuka
Awas! Lamun TDO340 dipaké pikeun pindah vol bahayatages (leuwih 30V), jalma terampil kudu masang alat dina kamar kalawan aksés dikawasa.
Panganteur
- Protokol: Modbus RTU
- lapisan fisik: garis serial RS-485
- Jumlah transceiver beus: dugi ka 63
- Kabel beus: Dipintal, dipayung, 2×0.5mm²
- waktos respon ≤ 50ms
Master response time-out ≥ Response time + Answer time Waktu jawaban gumantung kana jumlah bit jeung baud rate.
- Panyambung
- Komunikasi: 3.81mm pitch screwless pluggable pikeun 28 nepi ka 16 (AWG) / 0.081 nepi ka 1.31 (mm²) kawat
- Kaluaran relay: 5.08mm pitch screwless pluggable pikeun 26 nepi ka 14 (AWG) / 0.2 nepi ka 1.5 (mm²) kawat
- Garansi
- Mangsa jaminan: 3 taun
Indikator
Status alat dipintonkeun ku LED "Status":
- Lamun LED blinks unggal 1 detik, sensor jalan bener;
- Lamun LED blinks unggal 3 detik, euweuh komunikasi jeung controller;
- Lamun LED teu kedip-kedip, euweuh catu daya.
Unggal relay gaduh LED khusus pikeun nunjukkeun statusna. LED hurung hartina relay diaktipkeun (kontakna ditutup)
Pinout
- 5-pin konektor
- 1 + VDD (5 nepi ka 28)
- 2 GND
- 3 RS485+
- 4 RS485-
- 5 Terminator
- 8-pin konektor
- 1-2 Relay 1 NO kontak
- 3-4 Relay 2 NO kontak
- 5-6 Relay 3 NO kontak
- 7-8 Relay 4 NO kontak

Pamasangan
Numutkeun kana modbus.org, definisi MODBUS "Dua-Kawat" nyatakeun: "Solusi MODBUS dina jalur séri kedah nerapkeun antarmuka listrik "Dua-Kawat" saluyu sareng standar EIA/TIA-485. Dina topologi "Dua-Kawat" sapertos kitu, ngan hiji supir anu tiasa ngirimkeun iraha waé. Salaku tambahan, konduktor katilu kedah nyambungkeun beus - sadaya alat umum.
Topologi ranté daisy (linier) sareng kabel UTP/FTP disarankeun pisan pikeun sababaraha sénsor. Pikeun operasi ditangtoskeun tina panganteur nu, terminators (120 ohm resistors) kudu dipasang dina duanana tungtung beus. Alatna ngagaduhan résistor 120-ohm anu diwangun. Pikeun ngeureunkeun beus, terminal "RS485-" sareng "Term" kedah disingkat.
Setélan standar pabrik
- Pegatkeun sambungan catu daya.
- Pencét jeung tahan tombol "Setup".
- Bari nahan tombol, sambungkeun catu daya.
- Status LED bakal hurung salami 3 detik, teras hurung salami 7 detik, sareng tungtungna hurung deui.
- Leupaskeun tombol. Alat bakal balikan deui sareng setélan standar pabrik.
Pembaruan firmware
- Firmware alat tiasa diénggalan ku pengontrol Teracom kalayan ngadukung MODBUS RTU atanapi parangkat lunak MBRTUUpdate.
- Pikeun nempatkeun sensor dina modeu update, tuturkeun léngkah ieu:
- Pegatkeun sambungan sénsor ti beus jeung catu daya.
- Pencét jeung tahan tombol "Setup". Bari nahan tombol, sambungkeun deui catu daya.
- LED status bakal ON salila 3 detik. Salila 3 detik ieu, leupaskeun tombol terus pencét 3 kali pikeun] asup mode update.
- Dina modeu update, status LED bakal ON permanén.
- penting: sensor bisa diropéa ngan lamun éta hijina alat dina beus.
méja alamat Modbus
|
Ngaran ngadaptar |
Urang Sunda/W |
FC |
Alamat desimal | Ukuran data |
Default |
nilai valid |
|
| PDU | Logis | ||||||
| Ngayakeun registers | |||||||
| Alamat RS-485 | Urang Sunda/W | 3, 6, 16 | 10 | 40011 | uint16 | 1 | 1 nepi ka 247 |
| Laju Baud * | Urang Sunda/W | 3, 6, 16 | 11 | 40012 | uint16 | 19200 | 2400, 4800, 9600, 19200,
38400, 57600 |
| Parity, data, bit eureun * | Urang Sunda/W | 3, 6, 16 | 12 | 40013 | uint16 | 1 | 1=E81, 2=O81, 3=N81 |
| Kodeu alat | R | 3 | 14 | 40015 | uint16 | 0x00df | |
| Vérsi FW | R | 3 | 15 | 40016 | uint16 | ||
| Ngajual URL | R | 3 | 18 | 40019 | 64 bait UTF-8 |
teracomsystems.com |
|
| Nilai uji integer anu teu ditandaan | R | 3 | 91 | 40092 | uint16 | 999(0x03E7) | |
| Sadaya kaluaran relay, binér | Urang Sunda/W | 3 | 100 | 40101 | uint16 | 0b0000000000000000
nepi ka 0b0000000000001111 |
|
| Relay 1 kaluaran, binér | Urang Sunda/W | 3 | 101 | 40102 | uint16 | 0b0000000000000000
nepi ka 0b0000000000000001 |
|
| Relay 2 kaluaran, binér | Urang Sunda/W | 3 | 102 | 40103 | uint16 | 0b0000000000000000
nepi ka 0b0000000000000001 |
|
| Relay 3 kaluaran, binér | Urang Sunda/W | 3 | 103 | 40104 | uint16 | 0b0000000000000000
nepi ka 0b0000000000000001 |
|
| Relay 4 kaluaran, binér | Urang Sunda/W | 3 | 104 | 40105 | uint16 | 0b0000000000000000
nepi ka 0b0000000000000001 |
|
| Relays sanggeus kakuatan on | Urang Sunda/W | 3 | 200 | 40201 | uint16 | 0 | 0 - kabéh relays bakal balik deui ka nagara hasil set panungtungan
1 - sadaya relay bakal diaktipkeun 2 - sadaya relay bakal dinonaktipkeun 3 - relay bakal nuturkeun setélan dina registers 201 nepi ka 204 |
| Relay 1 sanggeus kakuatan on | Urang Sunda/W | 3 | 201 | 40202 | uint16 | 0 | 0 - relay bakal balik deui ka kaayaan terakhir anu suksés diatur 1 - relay bakal diaktipkeun 2 - relay bakal
dinonaktipkeun |
| Relay 2 sanggeus kakuatan on | Urang Sunda/W | 3 | 202 | 40203 | uint16 | 0 | 0 - relay bakal balik deui ka kaayaan junun diatur panungtungan
1 - relay bakal diaktipkeun |
| 2 - relay bakal
dinonaktipkeun |
|||||||
| Relay 3 sanggeus kakuatan on | Urang Sunda/W | 3 | 203 | 40204 | uint16 | 0 | 0 - relay bakal balik deui ka kaayaan terakhir anu suksés diatur 1 - relay bakal diaktipkeun 2 - relay bakal
dinonaktipkeun |
| Relay 4 sanggeus kakuatan on | Urang Sunda/W | 3 | 204 | 40205 | uint16 | 0 | 0 - relay bakal balik deui ka kaayaan terakhir anu suksés diatur 1 - relay bakal diaktipkeun 2 - relay bakal
dinonaktipkeun |
| Paripolah Relay1 upami teu aya komunikasi sareng alat salami waktos langkung lami tibatan Timeout (disetél dina register 305) | Urang Sunda/W | 3 | 301 | 40302 | uint16 | 0 | 0 - relay bakal tetep dina kaayaan panungtungan na; euweuh parobahan
1 - relay bakal diaktipkeun 2 - relay bakal dinonaktipkeun 3 - relay bakal switched ka kaayaan sabalikna pikeun durasi diatur dina register 306; pulsa bisa dipaké pikeun ngareset alat sejen. |
| Paripolah Relay2 upami teu aya komunikasi sareng alat salami waktos langkung lami tibatan Timeout (disetél dina register 305) | Urang Sunda/W | 3 | 302 | 40303 | uint16 | 0 | 0 - relay bakal tetep dina kaayaan panungtungan na; euweuh parobahan
1 - relay bakal diaktipkeun 2 - relay bakal dinonaktipkeun 3 - relay bakal switched ka kaayaan sabalikna pikeun durasi diatur dina register 306; Pulsa bisa dipaké pikeun ngareset alat sejen. |
| Paripolah Relay3 upami teu aya komunikasi sareng alat salami waktos langkung lami tibatan Timeout (disetél dina register 305) | Urang Sunda/W | 3 | 303 | 40304 | uint16 | 0 | 0 - relay bakal tetep dina kaayaan panungtungan na; euweuh parobahan
1 - relay bakal diaktipkeun 2 - relay bakal dinonaktipkeun 3 - relay bakal switched ka kaayaan sabalikna pikeun durasi diatur dina register 306; Pulsa bisa dipaké pikeun ngareset alat sejen. |
| Paripolah Relay4 upami teu aya komunikasi sareng alat salami waktos langkung lami tibatan Timeout (disetél dina register 305) | Urang Sunda/W | 3 | 304 | 40305 | uint16 | 0 | 0 - relay bakal tetep dina kaayaan panungtungan na; euweuh parobahan
1 - relay bakal diaktipkeun 2 - relay bakal dinonaktipkeun 3 - relay bakal switched ka kaayaan sabalikna pikeun durasi diatur dina register 306; Pulsa bisa dipaké pikeun ngareset alat sejen. |
| Waktos teu aya komunikasi sareng alat liwat MODBUS RTU | Urang Sunda/W | 3 | 305 | 40306 | uint16 | 0 | 0 - Waktos komunikasi Infinity 1 dugi ka 65535 -
timeout dina detik |
| Periode pulsa Watch-dog | Urang Sunda/W | 3 | 306 | 40307 | uint16 | 1 | 1 nepi ka 255 - période pulsa di
detik |
| Kaluaran diskrit | |||||||
| Relay 1 | Urang Sunda/W | 1, 5 | 1 | 2 | bit | 0 | 0 atawa 1 |
| Relay 2 | Urang Sunda/W | 1, 5 | 2 | 3 | bit | 0 | 0 atawa 1 |
| Relay 3 | Urang Sunda/W | 1, 5 | 3 | 4 | bit | 0 | 0 atawa 1 |
| Relay 4 | Urang Sunda/W | 1, 5 | 4 | 5 | bit | 0 | 0 atawa 1 |
- Alamat perpuluhan logika anu ditingalikeun diitung nganggo offset 1 (kaluaran diskrit) sareng 40001 (register nyekel).
- Alamat PDU - alamat sabenerna dipaké dina Unit Modbus Protocol Data, dikirimkeun ngaliwatan beus;
- Setelan bakal mawa pangaruh sanggeus balikan deui alat ku pareum, tur hurungkeun.
Daur ulang
- Daur ulang kabéh bahan lumaku.
- Ulah dispose tina sampah rumah tangga biasa.
INFORMASI LEUWIH
Dokumén / Sumberdaya
![]() |
TERACOM TDO340 Modbus RTU Relay Kaluaran Module [pdf] Manual pamaké TDO340 Modbus RTU Relay Kaluaran Module, TDO340, Modbus RTU Relay Kaluaran Module, Relay Kaluaran Module, Kaluaran Module |